FEATURES
  • Mean time between failures (MTBF) – 40,000 hours
  • Isolation switches for input, output and battery
  • SNMP communications and control options
  • Draw-out sub-assemblies and printed wiring boards
  • Built-in test (BIT) capability
  • On-line maintenance of batteries and battery charger
  • Key system LED status indicators.
  • LCD status display

Input
Voltage440 VAC nominal, 3 phase
Frequency60 Hz nominal
Output
Voltage115 VAC, 1 phase
Frequency60 Hz
Power Rating6 kVA
Power Backup TimeNumerous Durations Available
Efficiency80% at rated load
Number of Output Connectors6
Environmental
Operating Temperature10°C to 50°C / 50°F to 122°F
EMI/EMCMIL-STD-461D, CE101, CE102, CS101, CS114, CS116, RE101, RE102, RS101, RS103
VibrationMIL-STD-167/1, Type 1, 4 Hz to 33 Hz
Shock ResistanceMIL-S-901D, Grade A, Class I, Type A
Airborne NoiseMIL-STD-740-1, Grade A12
Cooling MethodForced air convection
Physical
Power Unit Dimensions
(LXWXH Inches)20.2 x 15.7 x 28 (bulkhead)
28 x 15 x 14 (8U) (rack)
(LXWXH mm)513 x 400 x 710 (bulkhead)
710 x 383 x 355 (8U) (rack)
Power Unit Weight (excluding batteries)
(LBS. Max)332 lbs
(KGS. Max)151 kgs