- Mean time between failures (MTBF) – 40,000 hours
- Isolation switches for input, output and battery
- SNMP communications and control options
- Draw-out sub-assemblies and printed wiring boards
- Built-in test (BIT) capability
- On-line maintenance of batteries and battery charger
- Key system LED status indicators.
- LCD status display
|
 |
|
| Voltage | 440 VAC nominal, 3 phase | | Frequency | 60 Hz nominal |
|
| Voltage | 115 VAC, 1 phase | | Frequency | 60 Hz | | Power Rating | 6 kVA | | Power Backup Time | Numerous Durations Available | | Efficiency | 80% at rated load | | Number of Output Connectors | 6 |
|
| Operating Temperature | 10°C to 50°C / 50°F to 122°F | | EMI/EMC | MIL-STD-461D, CE101, CE102, CS101, CS114, CS116, RE101, RE102, RS101, RS103 | | Vibration | MIL-STD-167/1, Type 1, 4 Hz to 33 Hz | | Shock Resistance | MIL-S-901D, Grade A, Class I, Type A | | Airborne Noise | MIL-STD-740-1, Grade A12 | | Cooling Method | Forced air convection |
|
| Power Unit Dimensions | | (LXWXH Inches) | 20.2 x 15.7 x 28 (bulkhead) 28 x 15 x 14 (8U) (rack) | | (LXWXH mm) | 513 x 400 x 710 (bulkhead) 710 x 383 x 355 (8U) (rack) | | Power Unit Weight (excluding batteries) | | (LBS. Max) | 332 lbs | | (KGS. Max) | 151 kgs |
|