- Isolation switches for input, output and battery
- Draw-out sub-assemblies and printed wiring boards
- Built-in test (BIT) capability
- LED status indication for input, output, back-up mode operation, low battery, over current, over temperature and unit shutdown
- Indicator and fault signals for remote control panel
|
 |
|
| Applicable Standards | MIL-STD-1399, Section 300 A, Type 1 / CS-F 24999 | | Voltage | 115 VAC nominal, 3 phase or 440 VAC nominal, 3 phase | | Frequency | 60 Hz nominal |
|
| Applicable Standards | MIL-STD - 1399 Section 300 A, Type 3, CS-F-24999 | | Voltage | 120 VAC, 3 phase | | Power Rating | 5 KW, minimum 0.8 power factor (lag) | | Frequency | 400 Hz | | Efficiency | 80% at rated load |
|
| Operating Temperature | 0°C to 50°C / 32°F to 122°F | | Relative Humidity | up to 95% | | EMI/EMC | MIL-STD-461C, Part 5, Surface Ships | | Vibration | MIL-STD-167-1, Type 1, 5 Hz to 15 Hz | | Shock Resistance | MIL-S-901C, Type A, Grade A, Class 1 | | Airborne Noise | MIL-STD-740-1, Class B | | Structureborne Noise | MIL-STD-740-2, Type 3 | | Cooling Method | Forced air convention |
|
| Dimensions | | | (LxWxH inches) | 27.7 x 19.6 x 39.6 | | (LxWxH mm) | 704 x 498 x 1006 | | Weight (excluding batteries) | 630 lbs. max | | 286 kg max |
|